Furnas 13AC060 three-pole manual motor starter/protector with an adjustable 4-6 A thermal trip range. It combines manual on/off motor switching, overload protection and short-circuit protection in a compact control-panel device.
| Specifications | |
|---|---|
| Model | 13AC060 |
| Condition | Surplus New |
| Other Specifications |
|---|
|
Catalog number: 13AC060 Device type: Manual motor starter/protector Current adjustment range: 4-6 A Visible dial settings: 4, 5 and 6 A Power poles: Three Line terminals: 1/L1, 3/L2 and 5/L3 Load terminals: 2/T1, 4/T2 and 6/T3 Normally open auxiliary contact: Terminals 13-14 Normally closed auxiliary contact: Terminals 21-22 Thermal trip threshold: 125% of dial setting Magnetic trip rating: 72 A Operating frequency: 50/60 Hz Utilization category: AC-3 Rated impulse withstand voltage: 6 kV Maximum operating voltage: 690 VAC |